Tuesday, 24 April 2018

Maintain safe distance from Electric Supply Lines


Maintain safe distance from Electric Supply Lines


As per current Indian Electricity Rules, any structure should be constructed keeping a safe distance from the nearby passing electric supply lines. If the structure is having extended parts like Verandah, Balcony etc. then the safe distance should be measured from it. The details of the safe distance to be maintained are furnished below.
Sl. No.Type of Electric Supply LineVertical DistanceHorizontal Distance
1)Low and medium voltage lines and service lines2.5m1.2m
2)High voltage lines up to and including 11 000 V3.7m1.2m
3)High voltage lines above 11 000 V and up to and including 33 000 V3.7m2.0m
4)Extra high voltage line beyond 33 000 V3.7m
(plus 0.3 m for every additional 33 000 V or part thereof)
2.0m
(plus 0.3 m for every additional 33 000 V or part thereof)
http://www.dreamhomeguide.in/maintain-safe-distance-from-electric-supply-lines/